Analogue E200 1-2 Loop (XP95/Discovery)

FEATURES
From 1-2 loops
Compliant with EN54 parts 2 and 4,BS EN 60950 and BS EN 50130 part 4
Full Apollo XP95 and Discovery compatibility
Automatic recognition of Apollo outstations
Extensive mode change options by day/night and special group allocation
Windows-based, full upload/download PC software package
500mA output per loop with highly stable voltage platform, even under mains-failed conditions
Fully networkable with other E200 panels
Powerful processing and extensive panel and loop I/O capability
User-friendly controls and a clear, unambiguous screen
Membrane facia with tactile switches
Complies with EMC and LVD Directives
Analogue E200 1-2 Loop (XP95/Discovery)
Click the image for technical data

Up to 248 user-definable panel inputs and relay/two-stage alarm outputs can be provided via expansions boards. Many useful testing and service functions are also provided. All events may be recorded on the optional printer and zonal indications are included as standard. There is a complete range of compatible accessories available to support the E200 panels to meet most customer requirements. The addition of a network card to the panel will allow monitoring, indication and control of the functions of a networked installation, allowing signals to be distributed around a large site.

The E200 analogue addressable panels are a powerful yet user-friendly series of control panels. They are designed to a high standard in compliance with EN54, parts 2 & 4. Each panel in this modular series has considerable processing ability but is easy to install, programme and operate. This is supported by comprehensive support documentation. Panels are housed in steel enclosures and are finished in hardwearing epoxy paint.

This panel is ideally suited to installations which require very complex sounder and control/shutdown functions. The panels are programmable to meet individual site requirements by means of a cause & effect matrix. This is downloaded from a PC, using the Cause & Effect Edit Programme. Text may be edited via a keyboard or downloaded from a PC.

The E200 has a 4 line x 20 character backlit LCD display, showing the first and most recent event. Other events may be reviewed using the More Messages facility. User controls are accessed by means of keyswitch-enabled membrane controls, with password protection for engineer purposes. Each panel has a high level of processing power and each loop has its own processor. The panel allows up to 126 addresses per loop. All addresses on a loop may be used for output functions, with 3 independently programmable output bits per address.

By using Apollo Discovery detectors, the system may be configured to automatically switch between heat and smoke detection at selected times of day or week. Additional facilities are also provided for temporary switching between smoke and heat detection to suit short-term changes in environmental conditions.

ORDER CODE      DESCRIPTION

BF/A/1L/E200 E200 1 Loop Control Panel
BF/A/2L/E200 E200 2 Loop Control Panel
BF/A/REP/E200 1-2 E200 Repeater Panel (1-2 Loop)
BF/A/3L/E200 E200 3 Loop Control Panel
BF/A/4L/E200 E200 4 Loop Control Panel
BF/A/REP/E200 3-4 E200 Repeater Panel (3-4 Loop)
DIMENSIONS

H 370mm W 325mm D 139mm
FINISHES AVAILABLE

White (Wh)

TECHNICAL SPECIFICATIONS
1 LOOP2 LOOP
Mains voltage230V AC +10% -6%
Mains failed fault battery current145mA170mA
Mains failed alarm battery current260mA285mA
Max. battery charging current1.5A
Alarm circuits2 @ 1A per circuit
Aux. supply20V-28V @ 500mA
Weight (excluding batteries)8kg
Dimensions370mm high x 325mm wide x 139mm deep



Base Lighting and Fire Ltd reserve the right to change specifications without prior notification.
All specifications and details are given in good faith but Base Lighting and Fire Ltd cannot be held responsible for any errors or omissions on this website

© 2005 Base Lighting and Fire Ltd





Home
Contact Us
Fire Alarm System Design
Emergency Lighting System Design
Fire Alarm Catalogue
Conventional Fire Equipment
Analogue Fire Equipment
  E100
  E200
  E300
  E400
  XP95
  Discovery
  Ancillaries
Emergency Lighting Catalogue
Disability Catalogue