| FEATURES |
 | From 1-2 loops |
 | Compliant with EN54 parts 2 and 4,BS EN 60950 and BS EN 50130 part 4 |
 | Full Apollo XP95 and Discovery compatibility |
 | Automatic recognition of Apollo outstations |
 | Extensive mode change options by day/night and special group allocation |
 | Windows-based, full upload/download PC software package |
 | 500mA output per loop with highly stable voltage platform, even under mains-failed conditions |
 | Fully networkable with other E200 panels |
 | Powerful processing and extensive panel and loop I/O capability |
 | User-friendly controls and a clear, unambiguous screen |
 | Membrane facia with tactile switches |
 | Complies with EMC and LVD Directives |
|
 Click the image for technical data
Up to 248 user-definable panel inputs and relay/two-stage alarm outputs can be provided via expansions boards. Many useful testing and service functions are also provided. All events may be recorded on the optional printer and zonal indications are included as standard. There is a complete range of compatible accessories available to support the E200 panels to meet most customer requirements. The addition of a network card to the panel will allow monitoring, indication and control of the functions of a networked installation, allowing signals to be distributed around a large site.
|
The E200 analogue addressable panels are a powerful yet user-friendly series of control panels. They are designed to a high standard in compliance with EN54, parts 2 & 4. Each panel in this modular series has considerable processing ability but is easy to install, programme and operate. This is supported by comprehensive support documentation. Panels are housed in steel enclosures and are finished in hardwearing epoxy paint.
This panel is ideally suited to installations which require very complex sounder and control/shutdown functions. The panels are programmable to meet individual site requirements by means of a cause & effect matrix. This is downloaded from a PC, using the Cause & Effect Edit Programme. Text may be edited via a keyboard or downloaded from a PC.
The E200 has a 4 line x 20 character backlit LCD display, showing the first and most recent event. Other events may be reviewed using the More Messages facility. User controls are accessed by means of keyswitch-enabled membrane controls, with password protection for engineer purposes. Each panel has a high level of processing power and each loop has its own processor. The panel allows up to 126 addresses per loop. All addresses on a loop may be used for output functions, with 3 independently programmable output bits per address.
By using Apollo Discovery detectors, the system may be configured to automatically switch between heat and smoke detection at selected times of day or week. Additional facilities are also provided for temporary switching between smoke and heat detection to suit short-term changes in environmental conditions.
|
| BF/A/1L/E200 | E200 1 Loop Control Panel |
| BF/A/2L/E200 | E200 2 Loop Control Panel |
| BF/A/REP/E200 | 1-2 E200 Repeater Panel (1-2 Loop) |
| BF/A/3L/E200 | E200 3 Loop Control Panel |
| BF/A/4L/E200 | E200 4 Loop Control Panel |
| BF/A/REP/E200 | 3-4 E200 Repeater Panel (3-4 Loop) |
|
H 370mm W 325mm D 139mm
White (Wh)
|
| TECHNICAL SPECIFICATIONS |
| 1 LOOP | 2 LOOP |
| Mains voltage | 230V AC +10% -6% |
| Mains failed fault battery current | 145mA | 170mA |
| Mains failed alarm battery current | 260mA | 285mA |
| Max. battery charging current | 1.5A |
| Alarm circuits | 2 @ 1A per circuit |
| Aux. supply | 20V-28V @ 500mA |
| Weight (excluding batteries) | 8kg |
| Dimensions | 370mm high x 325mm wide x 139mm deep |
|
|
Base Lighting and Fire Ltd reserve the right to change specifications without prior notification.
All specifications and details are given in good faith but Base Lighting and Fire Ltd cannot be held responsible for any errors or omissions on this website
© 2005 Base Lighting and Fire Ltd
|
|