Analogue E300 1-4 Loop (XP95/Discovery)

FEATURES
Modular, expandable and suited to a wide range of site applications
Full support of Apollo Discovery, XP95 and Xplorer protocols including all of the latest field devices
500mA available current per loop
Installer friendly 'Auto-learn' and 'Loop-detection' facility for uncomplicated, trouble-free, commissioning and faultfinding
Easily expandable using 'plug-in and play' loop driver cards that fully support all the latest Apollo field devices and provide 500mA loop current per loop for connection of loop driven sounders and other field devices
Robust, removable equipment chassis with plug-in connectors for simple fixing and cable termination
Integral EN54-4 power supply and charger
Device location text and cause and effect programming can be entered directly from the on-board alphanumeric keypad or a user-friendly Windows based configuration software
Optional on-board printer (multi-loop panels), Zone LED cards and internal peripheral expansion cards
Powerful extensive cause and effect programming capabilities, including variable delays and pulse options, double knock, latched and non-latch (non-fire) events, silenceable and non-silenceable outputs, investigation timers and sensitivities
Multiple programmable seven-day timers for flexible 'Day-Mode' sensitivity settings and operation of non-fire events
Analogue E300 1-4 Loop (XP95/Discovery)
Click the image for technical data

All standard panels and repeaters can be networked as a true peer-to-peer system simply by adding a network card.

The network system can share up-to 1000 zones and allows information from any input or output device to be passed over the network and displayed on any E200 control panel or remote terminal as required.

Approved to BS EN 54 part 2 & 4 by British Standards Institute (BSI) and bears the Kitemark.

Easy to use Windows based configuration and support tools including remote dial-up facilities over the standard telephone network using a low cost modem
Advanced 'Trace' diagnostics aids installers with fault-finding by providing highly accurate analogue measurement of all loop, sounder and auxiliary outputs

ORDER CODE      DESCRIPTION

BF/A/1-L/E300 E300 1 Loop Panel c/w Loop Card (Non-Expandable)
BF/A/2-L/E300 E300 2 Loop Panel c/w Loop Cards (Non-Expandable)
BF/A/4-L/E300 E300 4 Loop Panel c/w Loop Cards (Non-Expandable)
BF/A/1-8/E300 E300 1-8 Loop Panel no Loop Cards
BF/A/LC/XP95 E300 XP95 Loop Cards
BF/A/NC/E300E300 Network Card (all Panels are Fully Networkable)
ORDER CODE      DESCRIPTION

BF/A/REP/E300 E300 Repeater Panel
BF/A/8W/RO/C E300 8 Way Programmable Relay Output Card
BF/A/8W/RI/C E300 8 Way Programmable Relay Input Card
BF/A/PR/E300/F E300 On-Board Printer Fitted
BF/A/P-SOFT/K E300 Configuration Lead & Software

TECHNICAL SPECIFICATIONS
1 LOOP 1-2 LOOP 1-4 LOOP1-8 LOOP
Display Backlit 240 x 64 Graphical LCD
LED Indicators 3 Red (2 x Fire, 1 x Alarm), 1 Green (Power) & 12 Amber (Fault & System)
Number of Fire Zones 100 200 200200
(250 when Networked)
(1000 when networked)
Controls Alpha Numeric Keypad, Navigation Keys & System Keys for Reset, Mute, Silence/Re-sound & Evacuate
Protocols Apollo S90, XP95, Discovery & Xplorer
Number of Loops 1 1-21-41-8
Expandable via individual plug-in Loop Driver
Loop Current 500mA/Loop 500mA/Loop500mA/Loop500mA/Loop
On-Board Sounder Circuits 2 x 1 Amp Programmable 2 x 1 Amp Programmable2 x 1 Amp Programmable2 x 1 Amp Programmable
On-Board Relays 2 x 1 Amp 30V AC/DC Programmable2 x 1 Amp 30V AC/DC Programmable2 x 1 Amp 30V AC/DC Programmable4 x 1 Amp 30V AC/DC Programmable
Auxiliary Supply 1 x 24V 300mA1 x 24V 300mA1 x 24V 300mA2 x 24V 300mA
Open Collector/Logic Outputs 2 x Programmable8 x Programmable8 x Programmable8 x Programmable
(via optional 8-way Relay card)
Programmable Switch Inputs 8 Volt Free Digital Inputs (via optional 8-way Input card)
On-Board Power Supply 2 Amp4 Amp High Efficiency Switched Mode5 Amp High Efficiency Switched Mode2 x 5 Amp High Efficiency Switched Mode
Mains Supply 230V (+10%, -15% Tolerance) 50/60Hz AC 1 Amp maximum
Battery Capacity 24V - 4Ah min.
7Ah max.
BF/A/1-L/ADV - 12Ah max.
24V - 4Ah min. 17Ah Internal max.
38Ah max. with deep enclosure
48Ah max. with large enclosure
2 sets of
24V - 4Ah min.
38Ah max.
Charger Current 0.4 Amp2.4 Amp2.4 Amp2 x 2.4 Amp
Serial Ports 1 RS232 On-Board for PC, Modem or External Printer
Programming Via On-Board Keyboard or PC running Windows Tools
Event Log 1000 Event & Diagnostic + 500 Fire
Networking Optional plug-in Network Card
Printer (Option) Optional External SerialOptional On-Board or External Serial
Enclosure/Colour Steel IP40/Beige (textured)
Cable Entry (20mm Knock-outs) 7 x Top, 7 x Top Rear18 x Top, 9 x Top Rear & 2 x Bottom38 x Top, 9 x Top Rear
2 x Bottom
Enclosure Size
H x W x D
320 x 345 x 85475 x 450 x 115475 x 450 x 115950 x 450 x 188
Back Box Only Size
H x W x D
320 x 345 x 70(475 x 450 x 100 when recessing)950 x 450 x 170
Weight5Kg10.5Kg10.5Kg23Kg



Base Lighting and Fire Ltd reserve the right to change specifications without prior notification.
All specifications and details are given in good faith but Base Lighting and Fire Ltd cannot be held responsible for any errors or omissions on this website

© 2005 Base Lighting and Fire Ltd





Home
Contact Us
Fire Alarm System Design
Emergency Lighting System Design
Fire Alarm Catalogue
Conventional Fire Equipment
Analogue Fire Equipment
  E100
  E200
  E300
  E400
  XP95
  Discovery
  Ancillaries
Emergency Lighting Catalogue
Disability Catalogue