BS5266 -7:1999 Emergency lighting for premises ....
SITING OF FITTINGS AT POINTS OF EMPHASIS |
 | At each exit door |
 | Within 2m of stairs to direct light onto each step |
 | At each change of direction |
 | Within 2m of any change of level |
 | At each change of direction |
 | At each intersection |
 | Outside and within 2m of each final exit |
 | Within 2m of first aid equipment |
 | Within 2m of fire fi ghting equipment |
 | Within 2m of fire alarm call points |
 | At least two fittings in any compartment of the escape route
|
SITING OF ADDITIONAL FITTINGS FOR ILLUMINATION |
 | External areas outside the final exit |
 | Moving stairways and walkways |
 | Plant rooms |
 | Lift cars |
 | Covered car parks |
 | Toilets, lobbies and closets with a floor area over 8m square or with no natural light
|
THE LUMINOUS REQUIREMENTS |
 | Escape routes:
(Unobstructed 0.2 lux) / (may be obstructed 1 lux) |
 | Open areas: (0.5 lux minimum in core area) |
 | Additional areas: E.g. lifts, escalators. (As escape routes) |
 | High risk areas:
10% of normal illuminance but not less than 15 lux
|
DURATION |
 | This can vary from 1 to 3 hours |
 | The building cannot be re-occupied until a full duration recharge capacity has taken place |